Active , Confirmed Standard
Most Recent

ISO 19040-1:2018 (R2024)

Water quality
Determination of the estrogenic potential of water and waste water

Summary

This document specifies a method for the determination of the estrogenic potential of water and waste water by means of a reporter gene assay with genetically modified yeast strains Saccharomyces cerevisiae. This reporter gene assay is based on the activation of the human estrogen receptor alpha. This method is applicable to: — fresh water; — waste water; — aqueous extracts and leachates; — eluates of sediments (fresh water); — pore water; — aqueous solutions of single substances or of chemical mixtures; — drinking water. The limit of quantification (LOQ) of this method for the direct analysis of water samples is between 8 ng/l and 15 ng/l 17ß-estradiol equivalents (EEQ) based on the results of the international interlaboratory trial (see Annex F). The upper threshold of the dynamic range for this test is between 120 ng/l and 160 ng/l 17ß-estradiol equivalents (EEQ). Samples showing estrogenic potencies above this threshold have to be diluted for a valid quantification. Extraction and pre-concentration of water samples can prove necessary, if their estrogenic potential is below the given LOQ.

Notes

90.93 : Norme internationale confirmée

Technical characteristics

Publisher International Organization for Standardization (ISO)
Publication Date 08/07/2018
Confirmation Date 01/03/2024
Edition 1
Page Count 51
EAN ---
ISBN ---
Weight (in grams) ---
No products.